Instructions for labor protection when servicing boilers with electric heating

Occupational Safety and Health

Occupational Safety and Health / Standard instructions for labor protection

Comments on the article Comments on the article

Safe Operation

1. General requirements for labor protection

1.1. This instruction contains requirements for ensuring the safe operation of electrically heated boilers and is compiled on the basis of the manufacturer’s instructions for installation and operation

1.2. Persons at least 18 years of age who have undergone special training, a medical commission, have a certificate with a photo for the right to service electrically heated boilers and have Group III electrical safety are allowed to service boilers.

1.3. Re-inspection of the boiler room personnel is carried out at least once every 12 months.

1.4. When entering duty, personnel are required to familiarize themselves with the entries in the log, check the serviceability of the equipment and all boilers installed in the boiler room, the serviceability of the lighting and telephone, as well as the presence and serviceability of grounding.

Acceptance and delivery of duty must be documented by the operator with an entry in the shift log indicating the results of checking the boiler and related equipment (pressure gauges, safety valves, power supply devices, automation and electrical equipment).

1.5. It is not allowed to accept and hand over the shift during the liquidation of the accident.

1.6. Unauthorized persons access to the boiler room is allowed by the head of the enterprise.

1.7. The boiler room, boilers and all equipment, passages must be kept in good condition and proper cleanliness.

1.8. Doors for exiting the boiler room should open easily to the outside.

1.9. Boiler elements may only be repaired if there is no pressure at all. Before opening hatches and hatches located within the water space, the water from the boiler elements must be drained.

1.10. It is allowed to carry out work inside the furnaces and flues of the boiler only at a temperature not exceeding 50°C with the written permission of the person responsible for the good condition and safe operation of the boilers.

1.11. Before starting repair work, the furnace and gas ducts must be well ventilated, lit and reliably protected from possible penetration of gases and dust from gas ducts of operating boilers.

1.12. Before closing hatches and manholes, it is necessary to check if there are any foreign objects inside the boiler.

2. Preparation of the boiler for start-up

2.1. Before starting the boiler, check:

  • serviceability of electrical equipment, locking and control devices;
  • serviceability of instrumentation, fittings, nutritional devices;
  • fill the boiler with water up to the ignition level mark.

3. Boiler start

3.1 The boiler is started in manual mode.

The 1PP switch is set to the “MANUAL” position, and the power supply circuit of the EV is opened along the automatic control line.

Rectifier D1 is shunted by the contacts of switch 1PP and current relay 14PP is disconnected from the boiler control system. The automatic pressure control system is also disabled

3.2. The boiler power or pressure is controlled manually using the 3PP switch, which closes or opens the power supply circuit of the electronic device and, accordingly, opens or closes the computer. In this case, control is carried out visually using the readings of an ammeter, pressure gauge and level indicator.

4. Boiler operation

4.1. During operation, the operation of the boiler is carried out automatically. Heating and evaporation of water occurs due to the release of heat when passing through the boiler water between electrodes with different potentials. The total value of the current passing through the water depends on the depth of immersion of the electrodes and the resistivity of the water.

4.2. The automatic control system of the boiler provides the following functions: automatic maintenance of the specified power and, therefore, the steam output of the boiler at one of the following power levels 25%, 50%, 75%, 100% power, which corresponds to 60 A, 120 A, 180 A, 240 And, and also;

  • elimination of water hammer;
  • automatic maintenance of the specified pressure in the boiler;
  • work in manual mode;
  • short circuit protection;
  • protection against overfeeding the boiler with water;
  • automatic power off when opening the boiler casing doors.

4.3. The operation of the circuit for automatically maintaining the specified power is carried out using the 2PP switch, while the 1PP switch is set to the "automatic" position, and the 3PP switch to the "off" position.

4.4. The operation of the circuit for automatically maintaining the specified pressure in the boiler occurs in the following order. At a given steam flow rate and an increase in the level in the boiler, the pressure rises, when the pressure rises to the upper setting of the EKM, the 1RP relay is activated and the NO contacts close the power supply circuit of the EV, while the EMW opens, at the same time the 1RP relay becomes self-locking. The water level starts to drop, the current, steam production and, the pressure in the boiler decreases, the EKM min contacts close, the 2RP relay is activated and the NC contacts break the self-locking circuit of the 1RP relay, which is de-energized and the NO contacts break the power circuit. In this case, the EMW closes and the cycle repeats.

4.5. The protection of the boiler from overwatering is carried out in the following order.

At a certain height, a limit level sensor of the VU electrode type is installed in the column of level sensors. When the water reaches the sensor VU, the power circuit of the 4RP relay is closed, which closes the HP power circuit with NO contacts, the 1A automatic machine is triggered, and the boiler is de-energized.

4.6. The low water protection works in the same way.

4.7. While on duty, boiler personnel must monitor the serviceability of the boiler(s) and all boiler room equipment and strictly adhere to the established operating mode of the boiler. Malfunctions detected during equipment operation must be recorded in a shift log. Personnel must take corrective action. If it is impossible to eliminate malfunctions on your own, then you must inform the boiler house manager or the person responsible for the good condition and safe operation of the boilers.

4.8. Particular attention must be paid to:

  • to maintain a normal water level in the boiler and uniform supply of water to it. At the same time, the water level must not be allowed to fall below the set value, while replenishment is strictly prohibited;
  • to maintain normal steam pressure according to the pressure gauge (6kg / cm2);
  • on the amount of current flowing

4.9. Checking the health of the pressure gauge using three-way valves, checking the health of the safety valve by forced opening, purging the low points should be carried out by the operator every shift with an entry in the logbook.

4.10. All devices and devices for automatic control and safety of the boiler must be maintained in good condition and regularly checked, within the prescribed time limits, by the administration.

5. Boiler stop

5.1. It is carried out only on the written order of the person responsible for the good condition and safe operation of the boilers.

5.2. Turn off the power supply to the boiler with the handle of the machine 1AB

5.3. Close the main steam valve and open the drain.

5.4. Ventilate the furnace and gas pipelines.

5.5. Close the valve at the water inlet and outlet of the boiler.

5.6. Make an entry in the shift log when the boiler stops.

6. Emergency stop of the boiler

6.1. If a failure of one of the safety valves is detected.

6.2. If the steam pressure has increased by 10%, exceeding the permitted pressure, and does not decrease despite the measures taken (increased supply of water to the boiler, load reduction).

6.3. When the water level drops below the permissible mark. Make-up is strictly prohibited, which can lead to an explosion of the boiler.

6.4. When the level rises above the set mark.

6.5. In case of failure of all water-indicating devices.

6.6. When they fail all feed pumps.

6.7. Upon detection of the main elements of the boiler breaks, cracks, bulges.

6.8. When the power supply is interrupted.

6.9. In the event of a fire that threatens the operating personnel and the boiler.

In case of emergency shutdown of the boiler, it is necessary:

  • Turn off the boiler with the handle of the machine 1AB.
  • Monitor the water level in the boiler, close the main steam valve.
  • Make an entry in the watch log about the reasons and time of the boiler shutdown, notify the head of the boiler room about the emergency shutdown of the boiler.

In the event of a fire in the boiler room, the personnel must call the fire brigade and take all measures to extinguish it without stopping monitoring the boilers.

 We recommend interesting articles Section Standard instructions for labor protection:

▪ Pharmacist in the preparation of medicines. Standard instruction on labor protection

▪ Packing of food products. Standard instruction on labor protection

▪ Working with a trimmer for pruning shrubs. Standard instruction on labor protection

See other articles Section Standard instructions for labor protection.

Read and write useful comments on this article.

<< Back

Latest news of science and technology, new electronics:

Artificial leather for touch emulation 15.04.2024

In a modern technology world where distance is becoming increasingly commonplace, maintaining connection and a sense of closeness is important. Recent developments in artificial skin by German scientists from Saarland University represent a new era in virtual interactions. German researchers from Saarland University have developed ultra-thin films that can transmit the sensation of touch over a distance. This cutting-edge technology provides new opportunities for virtual communication, especially for those who find themselves far from their loved ones. The ultra-thin films developed by the researchers, just 50 micrometers thick, can be integrated into textiles and worn like a second skin. These films act as sensors that recognize tactile signals from mom or dad, and as actuators that transmit these movements to the baby. Parents' touch to the fabric activates sensors that react to pressure and deform the ultra-thin film. This ... >>

Petgugu Global cat litter 15.04.2024

Taking care of pets can often be a challenge, especially when it comes to keeping your home clean. A new interesting solution from the Petgugu Global startup has been presented, which will make life easier for cat owners and help them keep their home perfectly clean and tidy. Startup Petgugu Global has unveiled a unique cat toilet that can automatically flush feces, keeping your home clean and fresh. This innovative device is equipped with various smart sensors that monitor your pet's toilet activity and activate to automatically clean after use. The device connects to the sewer system and ensures efficient waste removal without the need for intervention from the owner. Additionally, the toilet has a large flushable storage capacity, making it ideal for multi-cat households. The Petgugu cat litter bowl is designed for use with water-soluble litters and offers a range of additional ... >>

The attractiveness of caring men 14.04.2024

The stereotype that women prefer "bad boys" has long been widespread. However, recent research conducted by British scientists from Monash University offers a new perspective on this issue. They looked at how women responded to men's emotional responsibility and willingness to help others. The study's findings could change our understanding of what makes men attractive to women. A study conducted by scientists from Monash University leads to new findings about men's attractiveness to women. In the experiment, women were shown photographs of men with brief stories about their behavior in various situations, including their reaction to an encounter with a homeless person. Some of the men ignored the homeless man, while others helped him, such as buying him food. A study found that men who showed empathy and kindness were more attractive to women compared to men who showed empathy and kindness. ... >>

Random news from the Archive

Formic acid bus 09.07.2017

Dutch student inventors have created the world's first bus that runs on formic acid, a cheap and environmentally friendly fuel.

Formic acid was first isolated from red wood ants (hence its name) in the XNUMXth century. Also in nature, it is found in some plants, for example, nettles and needles, and in the caustic secretions of bees. Usually it is obtained chemically in the production of acetic acid as a by-product. Formic acid is already used in many areas: the chemical industry (as a solvent), food (as a preservative), beekeeping (for pest control) and medicine (as an external pain reliever).

The fuel used by the new bus was named hydrozine (not to be confused with hydrazine) by the student inventors. It is a liquid that can be easily and relatively safely transported. Stations with formic acid will look and be used as the most common gas stations. The only difference is that the fuel in them is much cleaner. The bus will not emit any harmful gases - only water and CO2.

The fuel is created inside a device that Dutch students are now trying to patent. There, Hydrozine is decomposed into hydrogen and carbon dioxide with the help of a catalyst. The hydrogen is then added to a fuel cell, which it will react with to generate electricity that powers the engine.

The bus has an electric drive system developed by VDL. The tank is designed for 300 liters, so the researchers say the bus will be able to travel up to 200 kilometers. The vehicle is expected to be in active use by the end of this year.

Other interesting news:

▪ 3D surgeon helmet

▪ A new type of tablet from Lenovo

▪ Magic Leap 1 Mixed Reality Headset

▪ Yeast fungi will be sent into outer space

▪ Canon M-i1 Android Projector

News feed of science and technology, new electronics

 

Interesting materials of the Free Technical Library:

▪ section of the site Tools and mechanisms for agriculture. Article selection

▪ article Kazan orphans. Popular expression

▪ article What are the Ides of March? Detailed answer

▪ article Fire safety in the institution. Standard instruction on labor protection

▪ article Amplifier chip TDA7056, 3 watts. Encyclopedia of radio electronics and electrical engineering

▪ article Highly sensitive UHF converter. Encyclopedia of radio electronics and electrical engineering

Leave your comment on this article:

Name:


Email (optional):


A comment:





All languages ​​of this page

Home page | Library | Articles | Website map | Site Reviews

www.diagram.com.ua

www.diagram.com.ua
2000-2024