Menu English Ukrainian russian Home

Free technical library for hobbyists and professionals Free technical library


ENCYCLOPEDIA OF RADIO ELECTRONICS AND ELECTRICAL ENGINEERING
Free library / Encyclopedia of radio electronics and electrical engineering / Electrician

Section 4. Switchgears and substations

Switchgears and substations with voltages above 1 kV. Open switchgears

Free technical library

Encyclopedia of radio electronics and electrical engineering / Rules for the installation of electrical installations (PUE)

Comments on the article Comments on the article

4.2.45. In outdoor switchgear of 110 kV and above, passage should be provided for mobile assembly and repair mechanisms and devices, as well as mobile laboratories.

4.2.46. The connection of flexible wires in the spans should be carried out by crimping using connecting clamps, and the connections in loops at the supports, the connection of branches in the span and the connection to the hardware clamps - by crimping or welding. In this case, the connection of branches in the span is performed, as a rule, without cutting the wires of the span.

Soldering and twisting wires are not allowed.

Bolted connections are allowed only on the terminals of devices and on branches to arresters, surge arresters, coupling capacitors and voltage transformers, as well as for temporary installations for which the use of permanent connections requires a large amount of work on rewiring tires.

Insulator garlands for busbar suspension in outdoor switchgear can be single-circuit. If a single-chain garland does not meet the conditions of mechanical loads, then a double-chain garland should be used.

Separating (mortise) garlands are not allowed, with the exception of garlands, with the help of which high-frequency barriers are suspended.

The fastening of flexible busbars and cables in tension and suspension clamps in terms of strength must comply with the requirements given in 2.5.84.

4.2.47. Connections of rigid busbars in spans should be made by welding, and busbar connections of adjacent spans should be made using compensating devices attached to the busbars, as a rule, by welding. It is allowed to attach compensating devices to spans using bolted connections.

Branches from rigid tires can be made both flexible and rigid, and their connection to spans should be carried out, as a rule, by welding. Connection by means of bolted connections is permitted only upon justification.

4.2.48. Branches from the busbars of the outdoor switchgear, as a rule, should be located below the busbars.

Busbar suspension with one span over two or more sections or busbar systems is not allowed.

4.2.49. Wind and ice loads on tires and structures, as well as design air temperatures, must be determined in accordance with the requirements of building codes and regulations. In this case, the deflection of rigid tires should not exceed 1/80 of the span length.

When determining the loads on structures, the weight of a person with tools and mounting devices should additionally be taken into account when applying:

  • tension garlands of insulators - 2,0 kN;
  • supporting garlands - 1,5 kN;
  • support insulators - 1,0 kN.

The tension of the descents to the switchgear devices should not cause unacceptable mechanical stresses and unacceptable convergence of wires under the design climatic conditions.

4.2.50. The calculated mechanical forces transmitted during a short circuit by rigid tires to the support insulators should be taken in accordance with the requirements of Ch. 1.4.

4.2.51. The safety factor of mechanical strength under loads corresponding to 4.2.49 should be taken:

  • for flexible tires - not less than 3 in relation to their tensile strength;
  • for suspension insulators - at least 4 in relation to the guaranteed minimum breaking load of the entire insulator (mechanical or electromechanical, depending on the requirements of the standards for the type of insulator used);
  • for coupling fittings of flexible tires - at least 3 in relation to the minimum breaking load;
  • for rigid busbar support insulators - not less than 2,5 in relation to the guaranteed minimum breaking load of the insulator.

4.2.52. Supports for fastening outdoor switchgear tires should be calculated as intermediate or end in accordance with Ch. 2.5.

4.2.53. Layouts of outdoor switchgear 35 kV and above are recommended to be carried out without the upper tier of tires passing over the switches.

4.2.54. The smallest clear distances between non-insulated current-carrying parts of different phases, from non-insulated current-carrying parts to the ground, grounded structures and fences, as well as between non-insulated current-carrying parts of different circuits should be taken from Table. 4.2.5 (Fig. 4.2.3 - 4.2.12).

In the event that in installations located in high mountains, the distances between the phases increase in comparison with those given in Table. 4.2.5 according to the results of the corona test, the distances to grounded parts must be increased accordingly.

Table 4.2.5. The smallest clear distances from current-carrying parts to various elements of outdoor switchgear (substations) 10-750 kV, protected by arresters, and outdoor switchgear 220-750 kV, protected by surge arresters1), 2), 3), 4), 5), (in the denominator) (Fig. 4.2.3 - 4.2.12)

Figure number Distance name designation Insulating distance, mm, for rated voltage, kV
to 10 20 35 110 150 220 330 500 750
4.2.3 4.2.4 4.2.5 From current-carrying parts, live parts of equipment and insulation, to extended grounded structures and to permanent internal fences with a height of at least 2 m, as well as to stationary inter-cell screens and fire barriers Аf-z 200 300 400 900 1300 1800 1200 2500 2000 3750 3300 5500 5000
4.2.3 4.2.4 From current-carrying parts, live equipment and insulation elements to grounded structures: apparatus head - support, wire - stand, traverse, wire - ring, rod А1f-z 200 300 400 900 1300 1600 1200 2200 1800 3300 2700 5000 4500
4.2.3 4.2.4 4.2.11 Between current-carrying parts of different phases Аf-f 220 330 440 100 1400 2000 1600 1800 2200 4200 3400 8000 6500
4.2.5 4.2.7 From current-carrying parts, live parts of equipment and insulation, to permanent internal fences up to 1,6 m high and to transported equipment 'b' 950 1050 1150 1650 2050 2550 2000 3250 3000 4500 4100 6300 5800
4.2.8 Between the current-carrying parts of different circuits in different planes with the lower circuit being serviced and the upper one not being disconnected 'AT' 960 1050 1150 1650 2050 3000 2400 4000 3500 5000 3950 7000 6000
4.2.6 4.2.12 From unshielded current-carrying parts to the ground or to the roof of buildings with the greatest sagging of wires 'G' 2900 3000 3100 3600 4000 4500 3900 5000 4700 6450 6000 8200 7200
4.2.8 4.2.9 Between the current-carrying parts of different circuits in different planes, as well as between the current-carrying parts of different circuits horizontally when servicing one circuit and another not disconnected 'D1' 2200 2300 2400 2900 3300 3600 3200 4200 3800 5200 4700 7000 6500
4.2.10 4.2.12 From current-carrying parts to the upper edge of the external fence or to the building and structure 'D' 2200 2300 2400 2900 3300 3800 3200 4500 4000 5750 5300 7500 6500
4.2.11 From the contact and disconnector blade in the open position to the busbar attached to the second contact 'AND' 240 365 485 1100 1550 2200 1800 3100 2600 4600 3800 7500 6100

1. For insulation elements under a distributed potential, the insulation distances should be taken into account the actual values ​​of the potentials at different points on the surface. In the absence of data on the potential distribution, a straight-line law of the potential drop along the insulation from the full rated voltage (on the side of current-carrying parts) to zero (on the side of grounded parts) should be conventionally assumed.

2. The distance from current-carrying parts or insulation elements (on the side of live parts) under voltage to the dimensions of transformers transported by rail, it is allowed to take less than the size 'B', but not less than the size A1f-z.

3. The distances Af-z, A1f-z and Af-f for outdoor switchgear 220 kV and above, located at an altitude of more than 1000 m above sea level, must be increased in accordance with the requirements of state standards, and the distances Af-f, 'B' and 'D1' must be checked against corona restriction conditions.

4. For a voltage of 750 kV, the table gives the distances Af-f between parallel wires with a length of more than 20 m; distances Af-f, between screens, crossing wires, parallel wires up to 20 m long for 750 kV outdoor switchgear with arresters are 7000 mm, and for 750 kV outdoor switchgear with surge arresters - 5500 mm.

5. Surge arresters have a protective level for limiting switching surges phase - ground 1,8 Uph.


Rice. 4.2.3. The smallest distances in the light with rigid tires between current-carrying and grounded parts (Af-z, A1f-z) and between current-carrying parts of different phases (Af-f)


Rice. 4.2.4. The smallest clear distances with flexible busbars between current-carrying and grounded parts and between current-carrying parts of different phases located in the same horizontal plane

4.2.55. The smallest clear distances with rigid tires (see Fig. 4.2.3.) between the current-carrying and grounded parts Af-z and between the current-carrying parts of different phases Af-f should be taken according to Table. 4.2.5, and for flexible (see Fig. 4.2.4) - should be determined as follows:

Af-z.g = Af-z + α ; A1f-z = A1f-z.g + α ; Af-f.g = Af-f + α ;

where α=f sin(a); f - sag of wires at a temperature of +15 ºС, m; a=arctg(P/Q); Q - calculated load from the weight of the wire per 1 m of the length of the wire, daN/m; P - calculated linear wind load on the wire, daN/m; in this case, the wind speed is assumed to be 60% of the value selected in the calculation of building structures.

4.2.56. The smallest allowable clear distances between energized adjacent phases at the time of their closest approach under the action of short-circuit currents must be at least those given in Table. 2.5.17, taken according to the highest operating voltage.

In a flexible busbar made of several wires in a phase, in-phase spacers should be installed.

4.2.57. The smallest distances from live parts and insulators under voltage to permanent internal fences should be (Table 4.2.5, Fig. 4.2.5):

  • horizontally - not less than size 'B' with a fence height of 1,6 m and not less than Af-z size with a fence height of 2,0 m. The second option is recommended for use in cramped conditions of the substation site;
  • vertically - not less than the size of Af-z, measured in the plane of the fence from a point located at a height of 2,7 m from the ground.


Rice. 4.2.5. The smallest distances from current-carrying parts and insulation elements under voltage to permanent internal fences


Rice. 4.2.6. The smallest distances from unshielded current-carrying parts and from the lower edge of porcelain insulators to the ground

4.2.58. Current-carrying parts (terminals, buses, slopes, etc.) may not have internal fences if they are located above the planning level or ground communication structures at a height of at least the values ​​\u4.2.5b\u4.2.6bcorresponding to the size 'G' according to Table. XNUMX (Fig. XNUMX.).

Unshielded current-carrying parts connecting the capacitor of high-frequency communication, telemechanics and protection devices with the filter must be located at a height of at least 2,5 m. In this case, it is recommended to install the filter at a height that allows repair (adjustment) of the filter without removing voltage from the connection equipment.

Transformers and devices, in which the lower edge of porcelain (polymeric material) of insulators is located above the level of planning or ground communication facilities at a height of at least 2,5 m, it is allowed not to fence (see Fig. 4.2.6). At a lower height, the equipment must have permanent fences that meet the requirements of 4.2.29, located from transformers and apparatus at distances not less than those given in 4.2.57. Instead of permanent fences, it is allowed to install canopies that prevent the maintenance personnel from touching the insulation and live equipment.

4.2.59. Distances from unshielded current-carrying parts to the dimensions of machines, mechanisms and transported equipment must be at least size 'B' according to Table. 4.2.5 (Fig. 4.2.7.).


Rice. 4.2.7. The smallest distances from current-carrying parts to the transported equipment

4.2.60. The distances between the nearest unshielded current-carrying parts of different circuits must be selected from the condition of safe maintenance of one circuit with the second one not disconnected. When unshielded current-carrying parts of different circuits are located in different (parallel or perpendicular) planes, the vertical distances must be at least the size 'B', and horizontally - the size 'D1' according to Table. 4.2.5 (Fig. 4.2.8). In the presence of different voltages, the dimensions 'B' and 'D1' are taken at a higher voltage.

The size 'B' is determined from the condition of servicing the lower circuit with the upper one not disconnected, and the size 'D1' is the service of one circuit with the other not disconnected. If such maintenance is not provided, the distance between current-carrying parts of different circuits in different planes should be taken in accordance with 4.2.53; in this case, the possibility of wires approaching under operating conditions (under the influence of wind, ice, temperature) should be taken into account.


Rice. 4.2.8. The smallest distances between the current-carrying parts of different circuits located in different planes with maintenance of the lower circuit with the upper circuit not disconnected


Rice. 4.2.9. The smallest horizontal distances between the current-carrying parts of different circuits with the maintenance of one circuit while the other is not disconnected

4.2.61. The distances between the current-carrying parts and the upper edge of the outer fence must be at least the size 'D' according to the table. 4.2.5 (Fig. 4.2.10).


Rice. 4.2.10. The smallest distances from current-carrying parts to the upper edge of the outer fence

4.2.62. The distances from the moving contacts of the disconnectors in the off position to the grounded parts must be at least Af-z and A1f-z; before the busbar of its phase connected to the second contact - not less than the size 'Ж'; before busbars of other connections - not less than the size Af-f according to the table. 4.2.5 (Fig. 4.2.11).


Rice. 4.2.11. The smallest distances from the moving contacts of the disconnectors in the off position to grounded and current-carrying parts

4.2.63. The distances between the current-carrying parts of the outdoor switchgear and buildings or structures (ZRU, control room, transformer tower, etc.) horizontally must be at least 'D' size, and vertically with the greatest sagging of wires - not less than 'G' size according to Table. 4.2.5 (Fig. 4.2.12).


Rice. 4.2.12. The smallest distances between current-carrying parts and buildings and structures

4.2.64. Laying of overhead lighting lines, overhead communication lines and signaling circuits above and below the live parts of the outdoor switchgear is not allowed.

4.2.65. Distances from hydrogen warehouses to outdoor switchgear, transformers, synchronous compensators must be at least 50 m; to the VL supports - at least 1,5 support heights; to the buildings of the substation with the number of cylinders stored in the warehouse up to 500 pcs. - not less than 20 m, over 500 pcs. - not less than 25 m; to the outer fence of the substation - at least 5,5 m.

4.2.66. Distances from openly installed electrical devices to SS water coolers must be at least the values ​​given in Table. 4.2.6.

For areas with calculated outdoor temperatures below minus 36 ºС, given in Table. 4.2.6 distances should be increased by 25%, and with temperatures above minus 20 ºС - reduced by 25%. For reconstructed objects given in Table. 4.2.6 distances may be reduced, but not more than 25%.

Table 4.2.6. The smallest distance from openly installed electrical devices to SS water coolers

water cooler Distance, m
Sprinklers and open cooling towers 80
Tower and Single Fan Cooling Towers 30
Sectional Fan Cooling Towers 42

4.2.67. Distances from switchgear and substation equipment to ZRU buildings and other technological buildings and structures, to design bureaus, STK, SK are determined only by technological requirements and should not increase due to fire conditions.

4.2.68. Fire-prevention distances from oil-filled equipment with an oil mass of 60 kg or more in a piece of equipment to industrial buildings with room categories B1-B2, D and D, as well as to residential and public buildings must be at least:

  • 16 m - with the degree of fire resistance of these buildings I and II;
  • 20 m - at degree III;
  • 24 m - at degrees IV and V.

When installing oil-filled transformers with an oil mass of 60 kg or more, electrically connected to the equipment installed in these buildings, near the walls of industrial buildings with room category G and D, distances less than those indicated are allowed. At the same time, at a distance of more than 10 m from them and outside the sections with a width of 'B' (Fig. 4.2.13), there are no special requirements for the walls, windows and doors of buildings.

At a distance of less than 10 m to transformers within sections of width 'B', the following requirements must be met:

1) up to the height 'D' (up to the level of input of transformers) windows are not allowed;

2) with a distance 'r' of less than 5 m and fire resistance grades of buildings IV and V, the wall of the building must be made according to fire resistance grade I and rise above the roof made of combustible material by at least 0,7 m;

3) at a distance 'r' of less than 5 m and degrees of fire resistance of buildings I, II, III, as well as at a distance 'r' of 5 m or more without restriction on fire resistance at a height of 'd' to 'd' + 'e', ​​non-opening windows filled with reinforced glass or glass blocks with frames made of fireproof material; above 'd' + 'e' - windows that open into the building, with openings equipped with metal mesh from the outside with cells no larger than 25x25 mm;

4) at a distance of 'r' less than 5 m at a height of less than 'd', and at a 'r' of 5 m or more at any height, doors made of non-combustible or slow-burning materials with a fire resistance limit of at least 60 minutes are allowed;

5) ventilation inlets in the wall of the building at a distance 'r' less than 5 m are not allowed; exhaust openings with the emission of uncontaminated air within the specified limit are allowed at a height of 'd';

6) at a distance of 'd' from 5 to 10 m, ventilation holes in the enclosing structures of cable rooms on the side of transformers in a section with a width of 'B' are not allowed.

Shown in fig. 4.2.13 dimensions 'a'-'g' and 'A' are taken up to the most protruding parts of the transformers at a height of not more than 1,9 m from the ground. With a unit power of transformers up to 1,6 MVA, distances 'v' ≥1,5 m; 'e' ≥8 m; more than 1,6 MVA 'v' ≥2 m; 'e' ≥10 m. Distance 'b' is taken according to 4.2.217, distance 'd' must be at least 0,8 m.

The requirements of this paragraph also apply to outdoor PTS.


Rice. 4.2.13. Requirements for outdoor installation of oil-filled transformers in buildings with industries of categories G and D

4.2.69. To prevent oil spreading and fire spread in case of damage to oil-filled power transformers (reactors) with an oil quantity of more than 1 ton per unit, oil receivers, oil drains and oil collectors must be made in compliance with the following requirements:

1) the dimensions of the oil receiver must protrude beyond the dimensions of the transformer (reactor) by at least 0,6 m with an oil mass of up to 2 tons; 1 m with a mass of 2 to 10 tons; 1,5 m with a mass of 10 to 50 tons; 2 m with a mass of more than 50 tons. In this case, the size of the oil receiver can be taken less than 0,5 m from the side of a wall or partition located at a distance of less than 2 m from the transformer (reactor);

2) the volume of the oil receiver with oil removal should be designed for a one-time reception of 100% of the oil poured into the transformer (reactor).

The volume of the oil receiver without oil drainage should be designed to receive 100% of the volume of oil poured into the transformer (reactor) and 80% of water from fire extinguishing agents based on the irrigation of the oil receiver areas and side surfaces of the transformer (reactor) with an intensity of 0,2 l / s m2 within 30 minutes;

3) the arrangement of oil receivers and oil drains should exclude the flow of oil (water) from one oil receiver to another, the spread of oil over cable and other underground structures, the spread of fire, clogging of the oil drain and clogging it with snow, ice, etc.;

4) oil receivers for transformers (reactors) with an oil volume of up to 20 tons can be made without oil drainage. Oil receivers without oil drainage should be made of a recessed structure and closed with a metal grate, on top of which a layer of clean gravel or washed crushed granite with a thickness of at least 0,25 m, or non-porous crushed stone of another rock with particles from 30 to 70 mm should be poured. The level of the full volume of oil in the oil receiver must be at least 50 mm below the grate.

The removal of oil and water from the oil receiver without draining the oil must be provided by mobile means. In this case, it is recommended to perform a simple device to check the absence of oil (water) in the oil receiver;

5) oil receivers with oil drainage can be made both buried and not buried (the bottom is at the level of the surrounding layout). When making a recessed television receiver, the installation of side rails is not required if this ensures the volume of the oil receiver specified in clause 2.

Oil receivers with oil diversion can be performed:

with the installation of a metal grate on the oil receiver, on top of which gravel or crushed stone is poured with a layer thickness of 0,25 m;

without a metal grate with gravel filling on the bottom of the oil receiver with a layer thickness of at least 0,25 m.

An unburied oil receiver should be made in the form of side guards for oil-filled equipment. The height of the side railings should be no more than 0,5 m above the level of the surrounding layout.

The bottom of the oil receiver (submerged and non-buried) must have a slope of at least 0,005 towards the pit and be covered with cleanly washed granite (or other non-porous rock) gravel or crushed stone with a fraction of 30 to 70 mm. The thickness of the backfill must be at least 0,25 m.

The upper level of gravel (crushed stone) must be at least 75 mm below the upper edge of the side (when oil receivers are installed with side rails) or the level of the surrounding layout (when oil receivers are installed without side rails).

It is allowed not to backfill the bottom of the oil receivers over the entire area with gravel. At the same time, the installation of flame arresters should be provided for on systems for removing oil from transformers (reactors);

6) when installing oil-filled electrical equipment on a reinforced concrete floor of a building (structure), an oil drain is mandatory;

7) oil drains must ensure the removal of oil and water from the oil receiver used to extinguish a fire, by automatic stationary devices and hydrants to a fire-safe distance from equipment and structures: 50% of the oil and the full amount of water must be removed in no more than 0,25 hours Oil drains can be made in the form of underground pipelines or open cuvettes and trays;

8) oil collectors should be of a closed type and should contain the full volume of oil of individual equipment (transformers, reactors) containing the largest amount of oil, as well as 80% of the total (taking into account a 30-minute supply) water consumption from fire extinguishing equipment. Oil sumps must be equipped with a water presence alarm with a signal output to the control panel. The internal surfaces of the oil receiver, the guards of the oil receiver and the oil sump must be protected by an oil-resistant coating.

4.2.70. At substations with 110-150 kV transformers with a unit capacity of 63 MVA or more and transformers of 220 kV and above with a unit capacity of 40 MVA or more, as well as at substations with synchronous compensators for fire extinguishing, a fire-fighting water supply system powered by an existing external network or from an independent source of water supply. It is allowed to provide for water intake from ponds, reservoirs, rivers and other reservoirs located at a distance of up to 200 m from the substation using mobile fire fighting equipment instead of a fire-fighting water pipeline.

At substations with 35-150 kV transformers with a unit capacity of less than 63 MVA and 220 kV transformers with a unit capacity of less than 40 MVA, fire water and a reservoir are not provided.

4.2.71. KRUN and PTS of outdoor installation should be located on a planned site at a height of at least 0,2 m from the planning level with a service platform near the cabinets. In areas with a height of calculated snow cover of 1,0 m and above and a duration of its occurrence for at least 1 month, it is recommended to install outdoor KRUN and KTP at a height of at least 1 m.

The location of the device should provide convenient rolling out and transportation of transformers and the withdrawable part of the cells.

See other articles Section Rules for the installation of electrical installations (PUE).

Read and write useful comments on this article.

<< Back

Latest news of science and technology, new electronics:

The world's tallest astronomical observatory opened 04.05.2024

Exploring space and its mysteries is a task that attracts the attention of astronomers from all over the world. In the fresh air of the high mountains, far from city light pollution, the stars and planets reveal their secrets with greater clarity. A new page is opening in the history of astronomy with the opening of the world's highest astronomical observatory - the Atacama Observatory of the University of Tokyo. The Atacama Observatory, located at an altitude of 5640 meters above sea level, opens up new opportunities for astronomers in the study of space. This site has become the highest location for a ground-based telescope, providing researchers with a unique tool for studying infrared waves in the Universe. Although the high altitude location provides clearer skies and less interference from the atmosphere, building an observatory on a high mountain poses enormous difficulties and challenges. However, despite the difficulties, the new observatory opens up broad research prospects for astronomers. ... >>

Controlling objects using air currents 04.05.2024

The development of robotics continues to open up new prospects for us in the field of automation and control of various objects. Recently, Finnish scientists presented an innovative approach to controlling humanoid robots using air currents. This method promises to revolutionize the way objects are manipulated and open new horizons in the field of robotics. The idea of ​​controlling objects using air currents is not new, but until recently, implementing such concepts remained a challenge. Finnish researchers have developed an innovative method that allows robots to manipulate objects using special air jets as "air fingers". The air flow control algorithm, developed by a team of specialists, is based on a thorough study of the movement of objects in the air flow. The air jet control system, carried out using special motors, allows you to direct objects without resorting to physical ... >>

Purebred dogs get sick no more often than purebred dogs 03.05.2024

Caring for the health of our pets is an important aspect of the life of every dog ​​owner. However, there is a common assumption that purebred dogs are more susceptible to diseases compared to mixed dogs. New research led by researchers at the Texas School of Veterinary Medicine and Biomedical Sciences brings new perspective to this question. A study conducted by the Dog Aging Project (DAP) of more than 27 companion dogs found that purebred and mixed dogs were generally equally likely to experience various diseases. Although some breeds may be more susceptible to certain diseases, the overall diagnosis rate is virtually the same between both groups. The Dog Aging Project's chief veterinarian, Dr. Keith Creevy, notes that there are several well-known diseases that are more common in certain breeds of dogs, which supports the notion that purebred dogs are more susceptible to disease. ... >>

Random news from the Archive

Century CCA-DPHD4K6 active adapter 25.08.2016

The undoubted advantage of game consoles is the ability to connect them to large television panels, which allows you to immerse yourself in the atmosphere of the game. But it’s hard to use TVs as monitors - there are not so many graphics cards with full HDMI 2.0 support, but they often have a DisplayPort connector, which has already become, in fact, the de facto standard for modern computer monitors.

The Century CCA-DPHD4K6 active converter allows you to connect a PC equipped with a DisplayPort output to any modern TV equipped with an HDMI 2.0 input. This small box with a short DP cable is DisplayPort 1.2 compliant and can output up to 3840 x 2160 @ 60Hz in HDMI mode, which means at least version 2.0 support since HDMI 1.4 is limited to 4096 x 2160 at 30 Hz.

In other words, the manufacturer's statement about HDMI 1.4 support cannot be true if the device is really capable of operating in the aforementioned mode. The dimensions of the adapter are only 44,7 x 44,7 x 15,1 mm, it weighs only 34 grams and does not require additional power. The DisplayPort cable is 15 centimeters long, but either passive or active HDMI extenders can be used, depending on the length required. The converter does not require external power, the price of the novelty is $43.

Other interesting news:

▪ Turning light into matter

▪ Masked erythrocytes

▪ SHARP DV-HRW30 - VHS VCR, DVD and HDD recorder

▪ 6G data transmission record

▪ Radar in the temple

News feed of science and technology, new electronics

 

Interesting materials of the Free Technical Library:

▪ section of the site Car. Article selection

▪ article Tobacco smoking: impact on the human body, consequences. Basics of safe life

▪ article How old is wrestling? Detailed answer

▪ Ruskus article. Legends, cultivation, methods of application

▪ article Parametric sensors. Encyclopedia of radio electronics and electrical engineering

▪ article Charger with electronic protection. Encyclopedia of radio electronics and electrical engineering

Leave your comment on this article:

Name:


Email (optional):


A comment:





All languages ​​of this page

Home page | Library | Articles | Website map | Site Reviews

www.diagram.com.ua

www.diagram.com.ua
2000-2024