Menu English Ukrainian russian Home

Free technical library for hobbyists and professionals Free technical library


ENCYCLOPEDIA OF RADIO ELECTRONICS AND ELECTRICAL ENGINEERING
Free library / Encyclopedia of radio electronics and electrical engineering / Electrician

Section 2. Electrical equipment and electrical installations for general purposes

Chapter 2.10. Battery installations

Free technical library

Encyclopedia of radio electronics and electrical engineering / Rules for the technical operation of consumer electrical installations (PTE)

Comments on the article Comments on the article

2.10.1. This chapter applies to stationary installations of acid and alkaline batteries installed at the Consumer's premises.

2.10.2. Rechargeable batteries must be installed and maintained in accordance with the requirements of the rules for the design of electrical installations, safety rules for the operation of electrical installations, these Rules and the manufacturers' instructions.

The assembly of batteries, installation of batteries and their activation must be carried out by specialized organizations in accordance with the technical specifications for battery installations and the instructions of the manufacturers.

2.10.3. When operating batteries, the required level of voltage on the DC buses must be ensured in normal and emergency modes.

To ensure reliable battery operation, the manufacturer's instructions must be followed.

2.10.4. Installation of acid and alkaline batteries in the same room is not allowed.

2.10.5. The walls and ceiling of the battery room, doors and window frames, metal structures, shelving and other parts must be painted with acid-resistant (alkali-resistant) and alcohol-free paint. Ventilation ducts and fume hoods must be painted on the outside and inside.

For windows it is necessary to use frosted or coated with white adhesive paint glass.

2.10.6. To illuminate battery rooms, incandescent lamps installed in explosion-proof fittings must be used. One luminaire must be connected to the emergency lighting network.

Switches, sockets, fuses and circuit breakers must be located outside the battery room. Lighting electrical wiring must be carried out with a wire in an acid-resistant (alkali-resistant) sheath.

2.10.7. To reduce the evaporation of the electrolyte of an open-type acid battery, cover glasses or transparent acid-resistant plastic should be used, resting on the protrusions (tides) of the plates. The dimensions of these glasses should be smaller than the internal dimensions of the tank. For batteries with tank dimensions greater than 400 ´ 200 mm, it is allowed to use cover glasses of two or more parts.

2.10.8. To prepare an acid electrolyte, you must use sulfuric acid and distilled water, the quality of which is certified by a factory certificate or a chemical analysis report carried out in accordance with the requirements of state standards.

Preparation of acid electrolyte, storage and transportation of electrolyte and acid, bringing the battery into working condition must be carried out in accordance with the instructions of the manufacturer and the operating instructions for stationary lead-acid batteries.

2.10.9. The electrolyte level in acid batteries should be:

type="disc">
  • 10 - 15 mm above the upper edge of the electrodes for stationary batteries with surface-box plates of the SK type;
  • within 20 - 40 mm above the safety shield for stationary batteries with adhesive plates of type SN.
  • The density of the acid electrolyte, reduced to a temperature of 20 ° C, should be:

    type="disc">
  • for accumulators of the SK type - 1,205 ± 0,05 g/cm3;
  • for accumulators of type CH - 1,240 ± 0,005 g/cm3.
  • 2.10.10. When assembled into a battery, alkaline batteries must be connected in a series circuit using nickel-plated steel intercell jumpers.

    Alkaline batteries must be connected in a series circuit using copper conductor jumpers.

    The electrolyte level of sodium-lithium and potassium-lithium charged batteries should be 5 - 10 mm above the top edge of the plates.

    2.10.11. To prepare an alkaline electrolyte, potassium hydroxides or sodium hydroxides, lithium hydroxides, and distilled water that meet existing standards should be used.

    When preparing alkaline electrolyte and bringing the battery into working condition, the manufacturer's instructions must be followed.

    2.10.12. Battery cells must be numbered. Large numbers are applied to the front vertical wall of the tank with acid-resistant (alkali-resistant) paint. The first number in the battery indicates the element to which the positive bus is connected.

    2.10.13. When accepting a newly installed or overhauled battery, the following must be checked:

    type="disc">
  • capacity (10-hour discharge current or in accordance with the manufacturer’s instructions);
  • electrolyte quality;
  • electrolyte density and cell voltage at the end of battery charge and discharge;
  • battery insulation resistance to ground;
  • correct supply and exhaust ventilation.
  • Batteries must be put into service after they reach 100% of their rated capacity.

    2.10.14. Acid batteries operating in constant recharge mode must be operated without equalizing periodic recharges. To maintain all batteries in a fully charged state and to prevent sulfation of the electrodes, depending on the condition of the battery, but at least once a year, an equalizing charge (recharge) of the battery must be carried out until the steady-state value of the electrolyte density specified in clause 1 is achieved. , in all elements.

    The duration of the equalizing charge depends on the technical condition of the battery and must be at least 6 hours.

    At substations, battery performance should be checked by voltage drop during inrush currents.

    Equalizing recharge of the entire battery or its individual elements should be carried out only as needed.

    It is allowed to charge and discharge the battery with a current no higher than the maximum for this battery. The electrolyte temperature at the end of the charge should be no higher than 40 °C for SK type batteries and no higher than 35 °C for CH type batteries.

    2.10.15. Control discharges of acid batteries should be carried out in accordance with the operating instructions for stationary lead-acid batteries to determine the actual battery capacity as needed or once every 1 - 1 years.

    The discharge current value must be the same each time. The measurement results of control discharges must be compared with the measurement results of previous discharges.

    Acid batteries operating in constant recharge mode must be operated without training discharges. Discharge of individual batteries (or a group of them) can be carried out to perform repair work or when troubleshooting problems in them.

    2.10.16. The power and voltage of the charger must be sufficient to charge the battery to 90% of its rated capacity within no more than 8 hours with a previous 30-minute discharge.

    The recharger must ensure voltage stabilization on the battery buses with a deviation of ± 2%. Rectifier units used for charging and recharging batteries must be connected from the alternating current side through an isolation transformer.

    Additional battery batteries that are not constantly used in operation must have a separate charging device.

    The battery installation must be equipped with a voltmeter with a switch and ammeters in the charger, recharger and battery circuits.

    2.10.17. The procedure for operating the ventilation system in the battery room, taking into account specific conditions, must be determined by local instructions.

    The supply and exhaust ventilation of the battery room must be turned on before starting to charge the battery and turned off after the gases have been completely removed, but not earlier than 1,5 hours after the end of charging. The battery should be interlocked to prevent charging with a voltage of more than 2,3 V per cell when ventilation is turned off.

    2.10.18. The voltage on the operational DC buses under normal operating conditions can be maintained 5% higher than the rated voltage of the pantographs.

    2.10.19. All DC assemblies and rings must be powered from two sources.

    2.10.20. The insulation resistance of the battery is measured once every 1 months; its value, depending on the rated voltage of the battery, should be as follows:

    Battery voltage, V 24 48 60 110 220
    Insulation resistance Riz, kOhm, not less than 15 25 30 50 100

    DC buses must be equipped with a device for constant insulation monitoring, acting on the signal when the insulation resistance of one of the poles decreases to a value of 3 kOhm in a 24 V network, 5 kOhm in a 48 V network, 6 kOhm in a 60 V network, 10 kOhm in a 110 V network V, 20 kOhm in a 220 V network.

    Under operating conditions, the insulation resistance of the direct operating current network, measured periodically using an insulation monitoring device (or voltmeter), must be at least twice the minimum values ​​indicated above.

    2.10.21. If there is a ground fault (or a decrease in insulation resistance before the control device is triggered) in the operational current network, measures should be taken immediately to eliminate it.

    Carrying out work under voltage in the operational current network, if there is a ground fault in this network, is not allowed, with the exception of work to find the location of the fault.

    2.10.22. Maintenance of battery installations should be entrusted to a specialist trained in the rules of operating batteries.

    Each battery installation should have a battery log book to record the results of inspections and the amount of work performed.

    2.10.23. Analysis of the electrolyte of a working acid battery should be carried out annually using samples taken from control cells. The number of control elements is determined by the person responsible for the electrical equipment of the Consumer, depending on the condition of the battery, but not less than 10% of the number of elements in the battery. To be used as controls, different items must be assigned each year.

    During the control discharge, electrolyte samples are taken at the end of the discharge.

    To top up batteries, distilled water should be used, tested to be free of chlorine and iron.

    2.10.24. The battery can have no more than 5% lagging cells. The voltage of the lagging elements at the end of the discharge should differ from the average voltage of the remaining elements by no more than 1,5%.

    2.10.25. Inspection of batteries must be carried out according to a schedule approved by the person responsible for the Consumer’s electrical equipment, taking into account the following inspection frequency:

    type="disc">
  • duty staff - 1 time per day;
  • by a dedicated employee - 2 times a month;
  • responsible for electrical facilities - 1 time per month.
  • 2.10.26. During the current inspection, the following is checked:

    type="disc">
  • voltage, density and temperature of the electrolyte in the control elements (the voltage and density of the electrolyte in all and the temperature of the electrolyte in the control elements must be checked at least once a month);
  • voltage and current of recharging the main and additional batteries;
  • electrolyte level;
  • correct position of coverslips or filter plugs;
  • the integrity of the batteries, the cleanliness of the room;
  • ventilation and heating;
  • the presence of a small release of gas bubbles from the batteries;
  • level and color of sludge in accumulators with transparent tanks.
  • 2.10.27. Personnel servicing the battery installation must be provided with:

    type="disc">
  • technical documentation;
  • devices for monitoring the voltage of individual battery cells, density and temperature of the electrolyte;
  • special clothing;
  • special equipment and spare parts.
  • 2.10.28. Maintenance and repair of rectifier units and motor generators included in DC installations with a battery must be carried out in the manner established for this type of equipment.

    2.10.29. To carry out a major battery repair (replacement of a large number of batteries, plates, separators, disassembling the entire battery or a significant part of it), it is advisable to invite specialized repair organizations.

    The need for major battery repairs is determined by the person responsible for the electrical equipment of the Consumer.

    Major repairs of SK type batteries should, as a rule, be carried out no earlier than after 15 - 20 years of operation.

    Overhaul of SN type batteries is not carried out. Batteries of this type should be replaced no earlier than after 10 years of operation.

    See other articles Section Rules for the technical operation of consumer electrical installations (PTE).

    Read and write useful comments on this article.

    << Back

    Latest news of science and technology, new electronics:

    A New Way to Control and Manipulate Optical Signals 05.05.2024

    The modern world of science and technology is developing rapidly, and every day new methods and technologies appear that open up new prospects for us in various fields. One such innovation is the development by German scientists of a new way to control optical signals, which could lead to significant progress in the field of photonics. Recent research has allowed German scientists to create a tunable waveplate inside a fused silica waveguide. This method, based on the use of a liquid crystal layer, allows one to effectively change the polarization of light passing through a waveguide. This technological breakthrough opens up new prospects for the development of compact and efficient photonic devices capable of processing large volumes of data. The electro-optical control of polarization provided by the new method could provide the basis for a new class of integrated photonic devices. This opens up great opportunities for ... >>

    Primium Seneca keyboard 05.05.2024

    Keyboards are an integral part of our daily computer work. However, one of the main problems that users face is noise, especially in the case of premium models. But with the new Seneca keyboard from Norbauer & Co, that may change. Seneca is not just a keyboard, it is the result of five years of development work to create the ideal device. Every aspect of this keyboard, from acoustic properties to mechanical characteristics, has been carefully considered and balanced. One of the key features of Seneca is its silent stabilizers, which solve the noise problem common to many keyboards. In addition, the keyboard supports various key widths, making it convenient for any user. Although Seneca is not yet available for purchase, it is scheduled for release in late summer. Norbauer & Co's Seneca represents new standards in keyboard design. Her ... >>

    The world's tallest astronomical observatory opened 04.05.2024

    Exploring space and its mysteries is a task that attracts the attention of astronomers from all over the world. In the fresh air of the high mountains, far from city light pollution, the stars and planets reveal their secrets with greater clarity. A new page is opening in the history of astronomy with the opening of the world's highest astronomical observatory - the Atacama Observatory of the University of Tokyo. The Atacama Observatory, located at an altitude of 5640 meters above sea level, opens up new opportunities for astronomers in the study of space. This site has become the highest location for a ground-based telescope, providing researchers with a unique tool for studying infrared waves in the Universe. Although the high altitude location provides clearer skies and less interference from the atmosphere, building an observatory on a high mountain poses enormous difficulties and challenges. However, despite the difficulties, the new observatory opens up broad research prospects for astronomers. ... >>

    Random news from the Archive

    Turning ordinary material into a magnet 10.08.2020

    Ferromagnetism is a phenomenon that occurs in a material when most of the electrons in its atoms rotate in the same direction. In non-magnetic materials, oppositely directed electron spins usually cancel each other out, destroying the magnetic field.

    There are not many substances in the world that initially exhibit ferromagnetic properties. The most common of them are well known to us: these are iron, cobalt and nickel, as well as their alloys. That's why when creating electronic devices, the arsenal of engineers is so limited to these trinity.

    However, scientists claim that they managed to induce magnetism in a material that was not magnetic before. This is pyrite, "fool's gold" - a mineral that inexperienced miners often mistake for gold nuggets. Using a technique known as electrolytic gating, the researchers endowed it with uncharacteristic properties.

    First, they placed pyrite in contact with an electrolyte, after which they applied a weak - only 1 volt - discharge to the connection. This made it possible to move positively charged molecules in the area of ​​contact between pyrite and electrolyte, thereby creating a measurable magnetic force. Interestingly, as soon as the voltage was turned off, the magnetism also disappeared. This feature can help in the design of future generation electronics.

    “By applying voltage, we are actually injecting electrons into the material. It turns out that if a sufficiently high concentration of electrons is reached, then the material spontaneously acquires magnetic properties. Previously, all this was discussed only in theory, and we were damn surprised that our method worked. I’m sure that Since the experiment was successful with pyrite, then in the future we will be able to make other materials ferromagnetic," Chris Layton, lead author of the study, shared with the press.

    Other interesting news:

    ▪ Dirty air makes people stupid

    ▪ cloud in the universe

    ▪ Chip that combines USB Type-C and PD 2.0

    ▪ HP Pavilion 10z Mobile PC

    ▪ The taste of mother's milk

    News feed of science and technology, new electronics

     

    Interesting materials of the Free Technical Library:

    ▪ section of the site Funny puzzles. Article selection

    ▪ article Go for broke. Popular expression

    ▪ article Why did projects for diversion of northern rivers to the Volga appear and then disappear? Detailed answer

    ▪ Huangshan Mountain article. Nature miracle

    ▪ Antenna Beverage article. Encyclopedia of radio electronics and electrical engineering

    ▪ article Organization and operation of electrical installations. Electrical management. Operational management. Encyclopedia of radio electronics and electrical engineering

    Leave your comment on this article:

    Name:


    Email (optional):


    A comment:





    All languages ​​of this page

    Home page | Library | Articles | Website map | Site Reviews

    www.diagram.com.ua

    www.diagram.com.ua
    2000-2024