Section 3. Protection and automation

Automation and telemechanics. Automatic droop limit

Free technical library

Encyclopedia of radio electronics and electrical engineering / Rules for the installation of electrical installations (PUE)

Comments on the article Comments on the article

3.3.76. Automatic limitation of frequency reduction should be carried out in such a way that in case of any possible shortage of power in the power pool, power system, power center, the possibility of reducing the frequency below the level of 45 Hz is completely excluded, the operating time with a frequency below 47 Hz does not exceed 20 s, and with a frequency below 48,5 .60 Hz - XNUMX s.

3.3.77. The system of automatic frequency reduction limitation performs:

  • automatic frequency input reserve;
  • automatic frequency unloading (AFD);
  • additional unloading;
  • turning on the power supply of disconnected consumers during frequency recovery (CHAPV);
  • the allocation of power plants or generators with a balanced load, the allocation of generators to supply the own needs of power plants.

3.3.78. Automatic transfer at frequency reduction should be used in the first place in order to reduce the amount of disconnection or the duration of the interruption in the supply of consumers, if possible, and provides for:

  • mobilization of the included reserve at thermal power plants;
  • automatic start-up of hydraulic units in reserve;
  • automatic transition to the active mode of hydrogenerators operating in the mode of synchronous compensators;
  • automatic start-up of gas turbine units.

3.3.79. Automatic load shedding involves switching off consumers in small fractions as the frequency decreases (AFPI) or as the duration of the reduced frequency increases (AFPII).

AFC devices should be installed, as a rule, at substations of the power system. They can be installed directly at consumers under the control of the power system.

Load shedding volumes are set based on ensuring efficiency for any possible power shortages; the order of shutdown is chosen so as to reduce the damage from a power outage, in particular, a larger number of devices and queues of the AFC should be used, more responsible consumers should be connected to queues that are more distant in terms of the probability of operation.

The action of the ACR must be coordinated with the operation of the APV and AVR devices. It is unacceptable to reduce the volume of AFR due to the action of AVR devices or personnel.

3.3.80. Additional unloading devices should be used in those power systems or parts of the power system where especially large local power shortages are possible, in which the action of the AChRI devices is not effective enough in terms of the value and speed of unloading.

The need for additional unloading, its volume, as well as the factors by which it is triggered (disconnection of supply elements, active power shedding, etc.), is determined by the power system.

3.3.81. CHAR devices are used to reduce the power interruption of disconnected consumers in the conditions of frequency restoration as a result of the realization of generating power reserves, resynchronization or synchronization by a power outage.

When placing devices and distributing the load among the queues of the FACS, one should take into account the degree of responsibility of consumers, the likelihood of their shutdown by the action of the ARC, the complexity and duration of non-automatic restoration of power supply (based on the accepted procedure for servicing objects). As a rule, the order of turning on the load from the APW should be the reverse of that adopted for the AFC.

3.3.82. The allocation of power plants or generators with a balanced load, the allocation of generators to supply their own needs is applied:

  • to maintain the own needs of power plants;
  • to prevent complete shutdown of power plants in case of failure or insufficient efficiency of frequency reduction limiting devices according to 3.3.79 and 3.3.81;
  • to provide food for especially responsible consumers;
  • instead of additional unloading, when it is technically and economically feasible.

3.3.83. The need to use additional unloading, the volumes of the load to be switched off (during the AFR) and switched on (during the CAPV), the settings for time, frequency and other controlled parameters for frequency reduction limiting devices are determined during the operation of power systems in accordance with the PTE and other directive materials.

See other articles Section Rules for the installation of electrical installations (PUE).

Read and write useful comments on this article.

<< Back

Latest news of science and technology, new electronics:

A New Way to Control and Manipulate Optical Signals 05.05.2024

The modern world of science and technology is developing rapidly, and every day new methods and technologies appear that open up new prospects for us in various fields. One such innovation is the development by German scientists of a new way to control optical signals, which could lead to significant progress in the field of photonics. Recent research has allowed German scientists to create a tunable waveplate inside a fused silica waveguide. This method, based on the use of a liquid crystal layer, allows one to effectively change the polarization of light passing through a waveguide. This technological breakthrough opens up new prospects for the development of compact and efficient photonic devices capable of processing large volumes of data. The electro-optical control of polarization provided by the new method could provide the basis for a new class of integrated photonic devices. This opens up great opportunities for ... >>

Primium Seneca keyboard 05.05.2024

Keyboards are an integral part of our daily computer work. However, one of the main problems that users face is noise, especially in the case of premium models. But with the new Seneca keyboard from Norbauer & Co, that may change. Seneca is not just a keyboard, it is the result of five years of development work to create the ideal device. Every aspect of this keyboard, from acoustic properties to mechanical characteristics, has been carefully considered and balanced. One of the key features of Seneca is its silent stabilizers, which solve the noise problem common to many keyboards. In addition, the keyboard supports various key widths, making it convenient for any user. Although Seneca is not yet available for purchase, it is scheduled for release in late summer. Norbauer & Co's Seneca represents new standards in keyboard design. Her ... >>

The world's tallest astronomical observatory opened 04.05.2024

Exploring space and its mysteries is a task that attracts the attention of astronomers from all over the world. In the fresh air of the high mountains, far from city light pollution, the stars and planets reveal their secrets with greater clarity. A new page is opening in the history of astronomy with the opening of the world's highest astronomical observatory - the Atacama Observatory of the University of Tokyo. The Atacama Observatory, located at an altitude of 5640 meters above sea level, opens up new opportunities for astronomers in the study of space. This site has become the highest location for a ground-based telescope, providing researchers with a unique tool for studying infrared waves in the Universe. Although the high altitude location provides clearer skies and less interference from the atmosphere, building an observatory on a high mountain poses enormous difficulties and challenges. However, despite the difficulties, the new observatory opens up broad research prospects for astronomers. ... >>

Random news from the Archive

New LDO controller BD3574HFP 29.03.2007

New regulator with 5V/500mA output voltage and current, featuring high voltage tolerance (50V), high output voltage accuracy (+2%), lower on-resistance, high ESD immunity and short-circuit current protection circuit to reduce heat, ideal for use with microcontrollers and memory chips in automotive electronics.

The new chip also features low power consumption (30 µA in operating mode and 10 µA in standby mode).

Other interesting news:

▪ Powering wearable electronics with radio waves

▪ Ultra-bright yellow LED L-7113WYC

▪ Asus ROG Swift PG278Q Monitor with Nvidia G-Sync

▪ Video on e-books with color ink

▪ Compressed light for color photographs of nanomaterials

News feed of science and technology, new electronics

 

Interesting materials of the Free Technical Library:

▪ section of the site History of technology, technology, objects around us. Article selection

▪ article by Gertrude Stein. Famous aphorisms

▪ article What is a stalactite? Detailed answer

▪ article The operator of the braiding machine (weaver). Standard instruction on labor protection

▪ article Computer devices. Directory

▪ article Dancer Fatima. Focus Secret

Leave your comment on this article:

Name:


Email (optional):


A comment:





All languages ​​of this page

Home page | Library | Articles | Website map | Site Reviews

www.diagram.com.ua

www.diagram.com.ua
2000-2024