Menu English Ukrainian russian Home

Free technical library for hobbyists and professionals Free technical library


ENCYCLOPEDIA OF RADIO ELECTRONICS AND ELECTRICAL ENGINEERING
Free library / Encyclopedia of radio electronics and electrical engineering / Electrician

Section 1 General Rules

Grounding and protective measures for electrical safety. Grounding devices of electrical installations with voltage up to 1 kV in networks with dead-earthed neutral

Free technical library

Encyclopedia of radio electronics and electrical engineering / Rules for the installation of electrical installations (PUE)

Comments on the article Comments on the article

1.7.100. In electrical installations with a solidly grounded neutral, the neutral of a three-phase alternating current generator or transformer, the midpoint of a direct current source, one of the terminals of a single-phase current source must be connected to the ground electrode using a ground conductor.

An artificial earth conductor intended for neutral earthing should, as a rule, be located near the generator or transformer. For intrashop substations, it is allowed to place the ground electrode near the wall of the building.

If the foundation of the building in which the substation is located is used as natural grounding conductors, the transformer neutral should be grounded by attaching at least two metal columns or to embedded parts welded to the reinforcement of at least two reinforced concrete foundations.

When the built-in substations are located on different floors of a multi-storey building, the neutral grounding of the transformers of such substations must be carried out using a specially laid grounding conductor. In this case, the grounding conductor must be additionally connected to the building column closest to the transformer, and its resistance is taken into account when determining the spreading resistance of the grounding device to which the transformer neutral is connected.

In all cases, measures must be taken to ensure the continuity of the ground circuit and to protect the ground conductor from mechanical damage.

If a current transformer is installed in the PEN conductor connecting the neutral of the transformer or generator to the PEN bus of the switchgear with voltage up to 1 kV, then the grounding conductor must not be connected directly to the neutral of the transformer or generator, but to the PEN conductor, if possible immediately after the transformer current. In this case, the separation of the PEN conductor into PE and N conductors in the TN-S system must also be carried out behind the current transformer. The current transformer should be placed as close as possible to the neutral terminal of the generator or transformer.

1.7.101. The resistance of the grounding device to which the neutrals of the generator or transformer or the outputs of a single-phase current source are connected, at any time of the year should be no more than 2, 4 and 8 ohms, respectively, at line voltages of 660, 380 and 220 V of a three-phase current source or 380, 220 and 127 In a single-phase current source. This resistance must be provided taking into account the use of natural grounding conductors, as well as grounding conductors for repeated grounding of a PEN or PE conductor of an overhead line with a voltage of up to 1 kV with a number of outgoing lines of at least two. The resistance of the ground electrode located in close proximity to the neutral of the generator or transformer or the output of a single-phase current source should be no more than 15, 30 and 60 Ohms, respectively, at line voltages of 660, 380 and 220 V of a three-phase current source or 380, 220 and 127 V of a single-phase current source current.

With a specific earth resistance ρ > 100 Ohm m, it is allowed to increase the indicated norms by 0,01 ρ times, but not more than tenfold.

1.7.102. At the ends of overhead lines or branches from them longer than 200 m, as well as at the inputs of overhead lines to electrical installations, in which automatic power off is applied as a protective measure in case of indirect contact, re-grounding of the PEN conductor must be performed. In this case, first of all, natural grounding should be used, for example, underground parts of supports, as well as grounding devices designed for lightning surges (see Chap. 2.4).

The indicated repeated groundings are performed if more frequent groundings are not required under the conditions of lightning surge protection.

Re-grounding of the PEN conductor in DC networks must be carried out using separate artificial grounding conductors, which should not have metal connections with underground pipelines.

Grounding conductors for re-grounding the PEN conductor must have dimensions not less than those given in Table. 1.7.4.

Table 1.7.4. The smallest dimensions of grounding conductors and grounding conductors laid in the ground

Material Section profile Diameter, mm Cross-sectional area, mm Wall thickness, mm
Steel black Round:
for vertical earthing 16 - -
for horizontal earthing 10 - -
Rectangular - 100 4
Angular - 100 4
Pipe 32 - 3,5
Steel galvanized Round:
for vertical earthing 12 - -
for horizontal earthing 10 - -
Rectangular - 75 3
Pipe 25 - 2
Copper Round 12 - -
Rectangular - 50 2
Pipe 20 - 2
Multiwire rope 1,8* 35 -

* Diameter of each wire.

1.7.103. The total spreading resistance of ground electrodes (including natural ones) of all re-groundings of the PEN conductor of each overhead line at any time of the year should be no more than 5, 10 and 20 Ohms, respectively, at line voltages of 660, 380 and 220 V of a three-phase current source or 380, 220 and 127 V single-phase current source. In this case, the spreading resistance of the grounding conductor of each of the repeated groundings should be no more than 15, 30 and 60 ohms, respectively, at the same voltages.

With a specific earth resistance ρ > 100 Ohm m, it is allowed to increase the indicated norms by 0,01 ρ times, but not more than tenfold.

See other articles Section Rules for the installation of electrical installations (PUE).

Read and write useful comments on this article.

<< Back

Latest news of science and technology, new electronics:

Machine for thinning flowers in gardens 02.05.2024

In modern agriculture, technological progress is developing aimed at increasing the efficiency of plant care processes. The innovative Florix flower thinning machine was presented in Italy, designed to optimize the harvesting stage. This tool is equipped with mobile arms, allowing it to be easily adapted to the needs of the garden. The operator can adjust the speed of the thin wires by controlling them from the tractor cab using a joystick. This approach significantly increases the efficiency of the flower thinning process, providing the possibility of individual adjustment to the specific conditions of the garden, as well as the variety and type of fruit grown in it. After testing the Florix machine for two years on various types of fruit, the results were very encouraging. Farmers such as Filiberto Montanari, who has used a Florix machine for several years, have reported a significant reduction in the time and labor required to thin flowers. ... >>

Advanced Infrared Microscope 02.05.2024

Microscopes play an important role in scientific research, allowing scientists to delve into structures and processes invisible to the eye. However, various microscopy methods have their limitations, and among them was the limitation of resolution when using the infrared range. But the latest achievements of Japanese researchers from the University of Tokyo open up new prospects for studying the microworld. Scientists from the University of Tokyo have unveiled a new microscope that will revolutionize the capabilities of infrared microscopy. This advanced instrument allows you to see the internal structures of living bacteria with amazing clarity on the nanometer scale. Typically, mid-infrared microscopes are limited by low resolution, but the latest development from Japanese researchers overcomes these limitations. According to scientists, the developed microscope allows creating images with a resolution of up to 120 nanometers, which is 30 times higher than the resolution of traditional microscopes. ... >>

Air trap for insects 01.05.2024

Agriculture is one of the key sectors of the economy, and pest control is an integral part of this process. A team of scientists from the Indian Council of Agricultural Research-Central Potato Research Institute (ICAR-CPRI), Shimla, has come up with an innovative solution to this problem - a wind-powered insect air trap. This device addresses the shortcomings of traditional pest control methods by providing real-time insect population data. The trap is powered entirely by wind energy, making it an environmentally friendly solution that requires no power. Its unique design allows monitoring of both harmful and beneficial insects, providing a complete overview of the population in any agricultural area. “By assessing target pests at the right time, we can take necessary measures to control both pests and diseases,” says Kapil ... >>

Random news from the Archive

On the trail of chocolate 19.08.2007

Curious studies of the sense of smell in humans were conducted by Jess Porter, a graduate student at the University of Berkeley (USA).

She asked 32 undergraduate students to follow a 10-meter zigzag path with a chocolate-scented liquid on the grass of a lawn using their sense of smell. To ensure that the experimental subjects were not distracted by anything, they were blindfolded and their ears were plugged, leaving only the sense of smell. It turned out that two-thirds of the students, moving their noses from side to side, are able to complete the route in XNUMX minutes. After choosing four test subjects, they began to train them on the same exercise three times a day.

It turned out that the results are significantly improved with training. The possibility of "stereoscopic" sense of smell in humans (it is known in rats) was studied on 14 volunteers. With one nostril plugged, only a third made it to the end of the trail, and they did it 26% slower than with two nostrils.

The general conclusion: of course, the human sense of smell lags behind the canine, but it is much better than it is commonly thought, and lends itself to development.

Other interesting news:

▪ Hairpin RNA for genome editing

▪ Standalone fingerprint scanner

▪ pineapple leaf paper

▪ New cordless phone MD761

▪ Soothing soda

News feed of science and technology, new electronics

 

Interesting materials of the Free Technical Library:

▪ section of the site Normative documentation on labor protection. Article selection

▪ Demosthenes article. Popular expression

▪ article How the tsetse fly was exterminated on the island of Zanzibar? Detailed answer

▪ article Editor of film copies. Job description

▪ article Amplifier with common-mode mode stabilizer. Encyclopedia of radio electronics and electrical engineering

▪ article Guess the card. Focus Secret

Leave your comment on this article:

Name:


Email (optional):


A comment:





All languages ​​of this page

Home page | Library | Articles | Website map | Site Reviews

www.diagram.com.ua

www.diagram.com.ua
2000-2024