Annex 3. Standards for testing electrical equipment and apparatus for electrical installations of consumers

Oil and electromagnetic switches

Free technical library

Encyclopedia of radio electronics and electrical engineering / Rules for the technical operation of consumer electrical installations (PTE)

Comments on the article Comments on the article

K, T, M - are produced within the time limits established by the PPR system.

Name of the test Type of test Test norms Directions
10.1. Insulation resistance measurement:      
1) isolation of moving and guiding parts made of organic material К See table. 15 (Annex 3.1) Produced by a megohmmeter for a voltage of 2500 V
2) insulation of secondary circuits and windings of control electromagnets (hereinafter referred to as EMU) K, M Manufactured in accordance with Section 28 (at least 1 MΩ) Produced by a megohmmeter for a voltage of 1000 V
10.2. Power frequency overvoltage test: К Test duration - 1 min. -
1) support insulation and insulation relative to the body   The value of the test voltage is taken in accordance with Table. 5(Annex 3.1) For low-oil circuit breakers 6 - 10 kV, the isolation of the contact gap is also tested
2) isolation of secondary circuits and windings of EMU   Manufactured in accordance with Section 28 -
10.3. Bushing test K, M Tests are carried out in accordance with the instructions in section 9 -
10.4. Assessment of the state of intra-tank insulation and insulation of arc extinguishing devices of tank oil circuit breakers 35 kV К If tgδ of the bushings is reduced by more than 5%, then the insulation must be dried It is produced if, when measuring tgδ of the bushings on a fully assembled circuit breaker, increased values ​​​​are obtained compared to the standards given in Table. 14 (Annex 3.1)
10.5. DC resistance measurement: K, T, M    
1) oil switch contacts   The resistance of the current-carrying circuit should not exceed the values ​​\u16b\u3.1bspecified in Table. XNUMX (Appendix XNUMX). The norms for assigning resistance to individual sections of the current-carrying circuit are indicated in the factory instructions -
2) shunt resistors of arcing devices   The measured resistance values ​​must correspond to the factory data with the tolerances indicated in them. -
3) EMU windings   Must match factory specifications -
10.6. Checking the movement time of the moving parts of the circuit breaker К The obtained values ​​of the time from the issuance of the command to the moment of closing (opening) of the contacts of the oil switches must correspond to the values ​​\u16b\u3.1bspecified in Table. XNUMX (Annex XNUMX) -
10.7. Measurement of the stroke of the movable part of the switch, pressing (stroke) of the contacts when turned on, control of the simultaneity of closing and opening the contacts K, M The values ​​obtained must correspond to the values ​​\u16b\u3.1bspecified in table. XNUMX(Annex XNUMX) -
10.8. Checking the operation of the free release mechanism K, M The free trip mechanism must allow the opening operation to be carried out over the entire course of the contacts, i.e. at any time from the start of the power-on operation
The free disengagement mechanism is tested in operation with the drive in the fully engaged position and in two or three intermediate positions.
It is allowed not to check the operation of the mechanism of free disengagement of drives PP-61 and PP-67 in intermediate positions due to the danger of a sharp return of the hand drive lever
10.9. Checking the adjustment and installation characteristics of the switch mechanisms К The check is carried out in the scope and according to the norms of the factory instructions and passports of each type of drive and circuit breaker drives -
10.10. Undervoltage operation test К The minimum operating voltage of the tripping electromagnets of the oil circuit breaker drives must be at least 0,7 UMr. at DC and 0,65 UMr. with alternating current; closing electromagnets 0,85 UMr. at AC and 0,8 UMr. at direct current The lowest actuation voltage of control electromagnets of circuit breakers with spring drives must be determined at the operating preload (load) of the closing springs in accordance with the instructions of the factory instructions
10.11. Testing the circuit breaker by repeated closing and opening К Switching on, off and complex cycles (V-O, O-V, O-V-O) during repeated testing must be carried out at the rated voltage at the terminals of the electromagnets
Number of operations for each testing mode - (3 ± 5)
Two-, three-time testing in O-B and O-B-O cycles is carried out for circuit breakers intended for operation in the AR cycle
10.12. Testing transformer oil from circuit breaker tanks K, M Tank circuit breakers 110 kV and above:
a) breakdown voltage - not less than 60 kV for 110 kV switches and not less than 65 kV for 220 kV switches
b) the content of mechanical impurities - the absence
Breakdown voltage of transformer oil of tank circuit breakers:
for voltage up to 15 kV - 20 kV
for voltage up to 35 kV - 25 kV
For tank (multi-volume) circuit breakers for a voltage of 110 kV and above, tests are carried out when they perform the maximum allowable number of switching (off and on) short-circuit currents or loads
Oil from tank circuit breakers for voltages up to 35 kV and low-oil (low-volume) for all voltage classes after they have fulfilled the maximum allowable number of switching short-circuit currents or load currents is not subject to testing and must be replaced with fresh
10.13. Testing built-in current transformers М Produced in accordance with the instructions of paragraphs 20.1, 20.3.2, 20.5, 20.6, 20.7 section 20  
10.14. Thermal imaging control М Produced in accordance with established standards and manufacturer's instructions

See other articles Section Rules for the technical operation of consumer electrical installations (PTE).

Read and write useful comments on this article.

<< Back

Latest news of science and technology, new electronics:

The world's tallest astronomical observatory opened 04.05.2024

Exploring space and its mysteries is a task that attracts the attention of astronomers from all over the world. In the fresh air of the high mountains, far from city light pollution, the stars and planets reveal their secrets with greater clarity. A new page is opening in the history of astronomy with the opening of the world's highest astronomical observatory - the Atacama Observatory of the University of Tokyo. The Atacama Observatory, located at an altitude of 5640 meters above sea level, opens up new opportunities for astronomers in the study of space. This site has become the highest location for a ground-based telescope, providing researchers with a unique tool for studying infrared waves in the Universe. Although the high altitude location provides clearer skies and less interference from the atmosphere, building an observatory on a high mountain poses enormous difficulties and challenges. However, despite the difficulties, the new observatory opens up broad research prospects for astronomers. ... >>

Controlling objects using air currents 04.05.2024

The development of robotics continues to open up new prospects for us in the field of automation and control of various objects. Recently, Finnish scientists presented an innovative approach to controlling humanoid robots using air currents. This method promises to revolutionize the way objects are manipulated and open new horizons in the field of robotics. The idea of ​​controlling objects using air currents is not new, but until recently, implementing such concepts remained a challenge. Finnish researchers have developed an innovative method that allows robots to manipulate objects using special air jets as "air fingers". The air flow control algorithm, developed by a team of specialists, is based on a thorough study of the movement of objects in the air flow. The air jet control system, carried out using special motors, allows you to direct objects without resorting to physical ... >>

Purebred dogs get sick no more often than purebred dogs 03.05.2024

Caring for the health of our pets is an important aspect of the life of every dog ​​owner. However, there is a common assumption that purebred dogs are more susceptible to diseases compared to mixed dogs. New research led by researchers at the Texas School of Veterinary Medicine and Biomedical Sciences brings new perspective to this question. A study conducted by the Dog Aging Project (DAP) of more than 27 companion dogs found that purebred and mixed dogs were generally equally likely to experience various diseases. Although some breeds may be more susceptible to certain diseases, the overall diagnosis rate is virtually the same between both groups. The Dog Aging Project's chief veterinarian, Dr. Keith Creevy, notes that there are several well-known diseases that are more common in certain breeds of dogs, which supports the notion that purebred dogs are more susceptible to disease. ... >>

Random news from the Archive

Alpha Bonfire Pocket Bonfire 28.04.2021

Japanese brand for the manufacture of various outdoor gadgets and equipment The Brand Labo has introduced a compact model of the Alpha Bonfire electric fire. When folded, the device is a small aluminum box no larger than an average smartphone - the device measures 147x69x5 mm. And when the electric fire unfolds, it looks like five small aluminum sheets folded in the shape of the letter V in order to effectively and seamlessly hold any small pot or saucepan in its upper part.

And if the user wants to cook meat using such a pocket fire, then it will be enough for him to take out special grill grates from the inside of the structure, up to eight pieces, if necessary. What's more, the Alpha Bonfire pocket bonfire also has a built-in set of utensils ranging from spoon, fork and knife to chopsticks, which is quite convenient. We can say for sure that this model will surely find its user at the time of release.

Such a pocket fire is being developed as part of a corresponding campaign on the Indiegogo crowdfunding site and its initial cost is planned to be about $82 for those users who are already ready to donate funds for its development - for everyone else, the device will cost about $100 at the moment. of its release, about which, however, nothing concrete is known yet, although insiders will probably soon present something more revealing.

Other interesting news:

▪ XNUMXD echography

▪ Smart bracelet will track the composition of sweat

▪ Juggler - intellectual specialty

▪ Biometric lenses make vision three times sharper

▪ Greenland ice is melting fast

News feed of science and technology, new electronics

 

Interesting materials of the Free Technical Library:

▪ site section Low frequency amplifiers. Article selection

▪ article In those days when I was new ... Popular expression

▪ article Which country created a comprehensive genealogical database dating back to the 18th century? Detailed answer

▪ article Melon tree. Legends, cultivation, methods of application

▪ article Metal detector based on the principle of an electronic frequency meter, theory. Encyclopedia of radio electronics and electrical engineering

▪ article Transformation of three cards. Focus secret

Leave your comment on this article:

Name:


Email (optional):


A comment:





All languages ​​of this page

Home page | Library | Articles | Website map | Site Reviews

www.diagram.com.ua

www.diagram.com.ua
2000-2024